Plenum Cable 58616
Plenum Cable 58616

This picture is representative only and may not match the specific configuration of the product listed on this page. Please refer to the product specifications for more information on this part number and its exact configuration.
Download RoHS Certificate
Construction
Diameters (In) | ||||||||||||||||||||
1) Component 1 | 6 X 1 PAIR | |||||||||||||||||||
a) Conductor | 22 (7/30) AWG Tinned Copper | 0.030 | ||||||||||||||||||
b) Insulation | 0.007" Wall, Nom. FEP | 0.044 | ||||||||||||||||||
(1) Color Code | Alpha Wire Color Code A1 | |||||||||||||||||||
| ||||||||||||||||||||
c) Pair | 2/Cond Cabled Together | |||||||||||||||||||
(1) Twists: | 8.0 Twists/foot (min) | |||||||||||||||||||
Individually Applied: | ||||||||||||||||||||
d) Shield: | Foil Free Alum/Mylar Tape, 25% Overlap, Min. | |||||||||||||||||||
(1) Foil Direction | Foil Facing In | |||||||||||||||||||
(2) Drain Wire | 24 (7/32) AWG Tinned Copper | |||||||||||||||||||
2) Cable Assembly | 6 Components Cabled | |||||||||||||||||||
a) Twists: | 3.2 Twists/foot (min) | |||||||||||||||||||
b) Orientation: | Components to be arranged from INSIDE LAYER to OUTSIDE LAYER | |||||||||||||||||||
c) Core Wrap | Clear Mylar Tape, 25% Overlap, Min. | |||||||||||||||||||
3) Shield: | Alum/Mylar Tape, 25% Overlap, Min. | |||||||||||||||||||
a) Foil Direction | Foil Facing In | |||||||||||||||||||
b) Drain Wire | 24 (7/32) AWG Tinned Copper | |||||||||||||||||||
4) Jacket | 0.009" Wall, Nom.,PVDF | 0.263 (0.278 Max.) | ||||||||||||||||||
a) Color(s) | SLATE | |||||||||||||||||||
b) Print | ALPHA WIRE-* P/N 58616 6PR 22 AWG SHIELDED 125C (UL) TYPE CMP OR C(UL) TYPE CMP FT6 CE ROHS * = Factory Code [Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.] |
Applicable Specifications
1) UL | CMP | 125°C |
2) CSA International | FT6 | |
C(UL) TYPE CMP | 125°C | |
3) CE: | EU Low Voltage Directive 2014/35/EU |
Environmental
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3): | ||
This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. | ||
2) REACH Regulation (EC 1907/2006): | ||
This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. | ||
3) California Proposition 65: | This product may contain substances known to the State of California to cause Cancer or Reproductive Harm, but is exempt from labeling based on the Consent Judgement. See the Alpha Wire website for more information. |
Properties
Physical & Mechanical Properties | |
---|---|
1) Temperature Range | -25 to 125°C |
2) Bend Radius | 10X Cable Diameter |
3) Pull Tension | 91 Lbs, Maximum |
Electrical Properties | (For Engineering purposes only) |
1) Voltage Rating | 150 VRMS |
2) Characteristic Impedance | 43 Ω +/- 10 |
3) Inductance | 0.16 μH/ft, Nominal |
4) Mutual Capacitance | 38 pF/ft @1 kHz, Nominal |
5) Ground Capacitance | 68 pF/ft @1 kHz, Nominal |
6) Conductor DCR | 16.5 Ω/1000ft @20°C, Nominal |
7) Ind. Shield DC Resistance | 20.9 Ω/1000ft @20°C, Nominal |
8) OA Shield DCR | 13.4 Ω/1000ft @20°C, Nominal |
Other
Packaging | Flange x Traverse x Barrel (inches) |
a) 1000 FT | 18 x 9 x 8 Continuous length |
b) 500 FT | 12 x 10.5 x 5 Continuous length |
[Spool dimensions may vary slightly] |