Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
55026 Pair  UNSHIELDED  300  22  0.307  CA Prop 65, CE, CSA CMP, CSA FT6, UL AWM 20229, UL CMP 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 6 X 1 PAIR 
a) Conductor 22 (7/30) AWG TC 0.030
b) Insulation 0.010" Wall, Nom. FEP 0.050
(1) Color Code Alpha Wire Color Code A
Pair Color Pair Color Pair Color
1 BLACK-RED 3 BLACK-GREEN5 BLACK-BROWN
2 BLACK-WHITE 4 BLACK-BLUE6 BLACK-YELLOW
c) Pair 2/Cond Cabled Together 
(1) Twists: 8.0 Twists/foot (min) 
2) Cable Assembly 6 Components Cabled 
a) Twists: 3.4 Twists/foot (min) 
b) Core Wrap PTFE(skived) Tape, 25% Overlap, Min. 
3) Jacket 0.027" Wall, Nom.,FEP0.307 (0.324 Max.)
a) Tint Color(s) Natural Tan, Slate, Black, Yellow, Orange, Blue, Green, Red, White
b) Ripcord Para-Aramid fiber(Kevlar, Twaron or equal) 
c) Marker Tape ALPHA WIRE-*
XTRAGUARD(R) 5 - 22 AWG 150C (UL) CMP OR
AWM 20229 -- LLXXXXXX CSA CMP FT6 CE
ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL CMP 150°C
 AWM/STYLE 20229 150°C / 300 VRMS
2) CSA International CMP 150°C
 FT6 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range-80 to 200°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 66 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Mutual Capacitance13.7 pf/ft @1 kHz, Nominal
3) Characteristic Impedance103 Ω
4) Inductance0.18 µH/ft, Nominal
5) Conductor DCR16.6 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Xtra-Guard® 5 - Extreme Temperature and Chemical resistant to withstand the most hazardous environments High TemperatureLow TemperatureUltraviolet LightOil, Chemicals, Solvents, FuelsAbrasionDirect BurialEMI Noise

  • Extreme-performance cable featuring FEP insulation and jacketing for reliable performance in temperatures from -80°C to +200°C
  • Suitable for use in Class 1 cleanrooms
  • Recognized by the FDA, when sterilized, for food- and medical-grade applications
  • Impervious to oils, solvents, chemicals, fuels, and acids
  • Provides exceptional protection against EMI when Supra-Shield is specified

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire