Part # AWG  Construction Type  Stranding  # of Elements  Shielding  Jacket Diameter  Temperature Range  Voltage  Applicable Specifications 
77003 24  COND  7/32  UNSHIELDED  0.188  -50 to 105  600  CA Prop 65, CE, CSA AWM I/II A/B, CSA FT2, REACH Regulation (EC 1907/2006), ROHS - RoHS Compliance, UL AWM 21915 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 5 X 1 COND 
a) Conductor 24 (7/32) AWG Tinned Copper 0.024
b) Insulation 0.010" Wall, Nom. MPPE 0.044
(1) Color Code Alpha Wire Color Code E
Cond Color Cond Color Cond Color
1 BLACK 3 RED5 YELLOW
2 BROWN 4 ORANGE 
2) Cable Assembly 5 Components Cabled 
a) Twists: 9.6 Twists/foot (min) 
b) Orientation: Components to be arranged from INSIDE LAYER to OUTSIDE LAYER 
c) Core Wrap Nonwoven Polyester Tape, 25% Overlap, Min. 
3) Jacket 0.032" Wall, Nom.,MPPE0.188 (0.199 Max.)
a) Color(s) SLATE
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 77003 5C 24 AWG
ECOCABLE(R) RU AWM 21915 105C 600V
C(RU) AWM I/II A/B FT2 600V 105C
CE ROHS (SEQ FOOTAGE)
* = Factory Code
1) UL   
a) Component 1 AWM/STYLE 11231 105°C / 600 VRMS
b) Overall AWM/STYLE 21915 105°C / 600 VRMS
 Horizontal Flame 
2) CSA International C(RU) AWM I/II A/B FT2 105°C / 600 VRMS
3) Other Halogen-Free 
 NFPA 79 - 2015 Compliant 
4) CE:EU Low Voltage Directive 2014/35/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-50 to 105°C
2) Bend Radius 6X Cable Diameter
3) Pull Tension 17.6 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 15.1 pF/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.19 µH/ft, Nominal
4) Conductor DCR26 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 12 x 6 x 3.5 Continuous length
b) 100 FT 6.5 x 4 x 2.5 Continuous length
 [Spool dimensions may vary slightly]

EcoCable® 600 V Recyclable Control Cable:

EcoCable is the next generation of control cables. By combining better performance and minimum environmental impact, EcoCable uses its mPPE insulation and jacketing to provide all of the advantages in a smaller, lighter control cable.

  • Up to 47% smaller than PVC
  • Up to 65% lighter than PVC
  • Up to 87% lower outgassing
  • Zero Halogen
  • Capable of handling extreme temperatures