Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Thickness  Applicable Specifications 
F12005LW Conductor  UNSHIELDED  600  12  0.065  CA Prop 65, CE, CSA C(UL) CIC CONTROL, CSA C(UL) TC, CSA AWM I/II A/B, CSA FT4, UL EXPOSED RUN, UL MTW, UL OIL RES I/II, UL PLTC, UL SUN RES, UL TC, UL THHN 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 5 X 1 COND 
a) Conductor 12 (168(7x24)/34) AWG BC 0.104
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.146
(1) Print ALPHANUMERIC NUMBERS - 1-ONE ALTERNATING AND
INVERTED
(2) Color Code Alpha Wire Color Code LX
Cond Color Cond Color Cond Color
1 GREEN/YELLOW 3 DK. BLUE#25 DK. BLUE#4
2 DK. BLUE#1 4 DK. BLUE#3 
2) Cable Assembly 5 Components Cabled 
a) Twists: 3.0 Twists/foot (min) 
b) Core Wrap REMAY Tape, 25% Overlap, Min. 
3) Jacket 0.065" Wall, Nom.,TPE0.545+/- 0.022
a) Color(s) BLACK
b) Print ALPHA WIRE-* P/N F12005LW 5C 12 AWG (3.38mm2)
THHN SERIES F (UL) TYPE TC-ER 90C 600V
OIL RES I/II SUN RES OR TYPE PLTC 90C OR C(UL) CIC
CONTROL/TC 90C PVC/NYLON INS FT4 12 AWG
--- LLXXXXXX CSA AWM I/II A/B 90C 600V FT4
CE ROHS (DATE CODE) (SEQ FOOTAGE)
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL   
a) Component 1 MTW 90°C Dry / 60°C Wet / 600 VRMS
 THHN 90°C / 600 VRMS
b) Overall TC 90°C / 600 VRMS
 EXPOSED RUN 
 SUN RES 
 PLTC 90°C
 OIL RES I/II 
2) CSA International AWM I/II A/B 90°C / 600 VRMS
 FT4 
 C(UL) CIC CONTROL 90°C / 600V VRMS
 C(UL) TC 90°C / 600V VRMS
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C(static), -5 to 90°C (dynamic)
2) Bend Radius 10X Cable Diameter(static), 10X Cable Diameter(dynamic)
3) Pull Tension 262 Lbs, Maximum
4) Sunlight Resistance Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 35 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.16 µH/ft, Nominal
4) Conductor DCR1.65 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Alpha Wire's Series F continuous flex control cable offers industry-leading mechanical and electrical performance for high-flex cable track applications.

Series F Key features:

  • Up to 20 million continuous rolling flex cycles
  • 18 – 8 AWG
  • 3 – 65 conductors
  • PVC/nylon insulation
  • Thermoplastic elastomer jacket
  • UL Type TC-ER (600 V)
  • UL Type PLTC (300 V) (18-12AWG only)
  • Sunlight resistant

Request a Sample Download Brochure Consult a Cable Expert