Part # Type  AWG  Voltage  Shielding  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
M8524010 Pair  14  600  FOIL  PVC  PVC/NYLON  0.333  UL DIRECT BURIAL, UL SUN RES, UL TC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 1 X 1 PAIR 
a) Conductor 14 (7/.0242) AWG BC 0.073
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.115
(1) Color Code Alpha Wire Color Code Q
Pair Color Pair Color Pair Color
1 BLACK-WHITE   
c) Pair 2/Cond Cabled Together 
(1) Twists: 3.7 Twists/foot (min) 
(2) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
2) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing In 
b) Drain Wire 16 (7/.0192) AWG TC 
3) Jacket 0.048" Wall, Nom.,PVC0.333 (0.348 Max.)
a) Color(s) BLACK
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N M8524010 1PR 14 AWG
EXXXXXX (UL) TYPE TC 600V 90C DRY 75C WET
SUN. RES. DIR. BUR. CE ROHS
* = Factory Code
1) UL SUN RES 
 DIRECT BURIAL 
 TC 90°C Dry/ 60°C Wet
2) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 85 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Mutual Capacitance56 pf/ft @1 kHz, Nominal
3) Ground Capacitance101 pf/ft @1 kHz, Nominal
4) Characteristic Impedance39 Ω
5) Inductance0.17 µH/ft, Nominal
6) Conductor DCR2.6 Ω/1000ft @20°C, Nominal
7) OA Shield DCR4 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 18 x 12 x 8 Continuous length
b) 500 FT 12 x 12 x 3.5 Continuous length
c) 100 FT 12 x 4.5 x 3.5 Continuous length
d) Bulk(Made-to-order) 
 [Spool dimensions may vary slightly]

Alpha Essentials Tray Cable:

Built to withstand the harshest environments for your communication and control needs, Alpha Essentials tray cables present the perfect solution. We offer both CSA and UL ratings to meet the most stringent industrial applications.  Alpha Wire tray cables come in a variety of configurations which allow for faster installation without the costly need of conduit. 

 