Part # Type  AWG  Voltage  Shielding  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
M3842 Conductor  16  600  UNSHIELDED  37  PVC  PVC/NYLON  0.869  CA Prop 65, UL DIRECT BURIAL, UL SUN RES, UL TC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 37 X 1 COND 
a) Conductor 16 (7/.0192) AWG BC 0.058
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.100
(1) Color Code Alpha Wire Color Code J
Cond Color Cond Color Cond Color
1 BLACK 14 ORANGE/RED27 BLACK/YELLOW
2 RED 15 YELLOW/RED28 RED/YELLOW
3 BLUE 16 BROWN/RED29 BLUE/YELLOW
4 ORANGE 17 BLACK/BLUE30 ORANGE/YELLOW
5 YELLOW 18 RED/BLUE31 BROWN/YELLOW
6 BROWN 19 ORANGE/BLUE32 BLACK/BROWN
7 RED/BLACK 20 YELLOW/BLUE33 RED/BROWN
8 BLUE/BLACK 21 BROWN/BLUE34 BLUE/BROWN
9 ORANGE/BLACK 22 BLACK/ORANGE35 ORANGE/BROWN
10 YELLOW/BLACK 23 RED/ORANGE36 YELLOW/BROWN
11 BROWN/BLACK 24 BLUE/ORANGE37 BLACK
12 BLACK/RED 25 YELLOW/ORANGE 
13 BLUE/RED 26 BROWN/ORANGE 
2) Cable Assembly 37 Components Cabled 
a) Twists: 1.1 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.083" Wall, Nom.,PVC0.869 (0.912 Max.)
a) Color(s) BLACK
b) Print ALPHA WIRE-* P/N M3842 37C 16 AWG
EXXXXXX (UL) TYPE TC 600V 90C DRY 75C WET
SUN RES DIR BUR CE ROHS
* = Factory Code
1) UL TC 90°C / 600 VRMS
 SUN RES 
 DIRECT BURIAL 
2) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 751 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 30 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.18 µH/ft, Nominal
4) Conductor DCR4.2 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 48 x 26 x 18 Continuous length
b) 500 FT 30 x 14 x 12 Continuous length
c) 100 FT 24 x 14 x 12 Continuous length
d) Bulk(Made-to-order) 
 [Spool dimensions may vary slightly]

Alpha Essentials Tray Cable:

Built to withstand the harshest environments for your communication and control needs, Alpha Essentials tray cables present the perfect solution. We offer both CSA and UL ratings to meet the most stringent industrial applications.  Alpha Wire tray cables come in a variety of configurations which allow for faster installation without the costly need of conduit. 

 