Part # Type  AWG  Voltage  Shielding  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
M33858 Conductor  14  600  FOIL  19  PVC  PVC/NYLON  0.709  CA Prop 65, UL DIRECT BURIAL, UL SUN RES, UL TC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 19 X 1 COND 
a) Conductor 14 (7/.0242) AWG BC 0.073
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.115
(1) Color Code Alpha Wire Color Code J
Cond Color Cond Color Cond Color
1 BLACK 8 BLUE/BLACK15 YELLOW/RED
2 RED 9 ORANGE/BLACK16 BROWN/RED
3 BLUE 10 YELLOW/BLACK17 BLACK/BLUE
4 ORANGE 11 BROWN/BLACK18 RED/BLUE
5 YELLOW 12 BLACK/RED19 ORANGE/BLUE
6 BROWN 13 BLUE/RED 
7 RED/BLACK 14 ORANGE/RED 
2) Cable Assembly 19 Components Cabled 
a) Twists: 1.4 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing In 
b) Drain Wire 16 (7/.0192) AWG TC 
4) Jacket 0.063" Wall, Nom.,PVC0.709 (0.742 Max.)
a) Color(s) BLACK
b) Print ALPHA WIRE-* P/N M33858 19C 14 AWG
EXXXXXX (UL) TYPE TC 600V 90C DRY 75C WET
SUN RES DIR BUR CE ROHS
* = Factory Code
1) UL TC 90°C / 600 VRMS
 SUN RES 
 DIRECT BURIAL 
2) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 632 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 50 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Ground Capacitance90 pf/ft @1 kHz, Nominal
4) Inductance0.17 µH/ft, Nominal
5) Conductor DCR2.6 Ω/1000ft @20°C, Nominal
6) OA Shield DCR3.5 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 36 x 14 x 12 Continuous length
b) 500 FT 30 x 14 x 12 Continuous length
c) 100 FT 16 x 11 x 8 Continuous length
d) Bulk(Made-to-order) 
 [Spool dimensions may vary slightly]

Alpha Essentials Tray Cable:

Built to withstand the harshest environments for your communication and control needs, Alpha Essentials tray cables present the perfect solution. We offer both CSA and UL ratings to meet the most stringent industrial applications.  Alpha Wire tray cables come in a variety of configurations which allow for faster installation without the costly need of conduit. 

 

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources