Part # Type  AWG  Voltage  Shielding  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
5660   16  600  SupraShield (Premium Foil/Braid)  PVC  PVC/NYLON  0.381  CSA AWM I/II A/B, CSA FT4, UL 1063, UL 1277 Type TC-ER, UL 1581, UL DIRECT BURIAL, UL EXPOSED RUN, UL MTW, UL SUN RES 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 4 X 1 COND 
a) Conductor 16 (26/30) AWG BC 0.060
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.102
(1) Color Code Alpha Wire Color Code KX
Cond Color Cond Color Cond Color
1 GREEN/YELLOW 3 BLACK#2 
2 BLACK#1 4 BLACK#3 
2) Cable Assembly 4 Components Cabled 
a) Twists: 3.4 Twists/foot (min) 
3) Shield: A/P/A Tape, 25% Overlap, Min. 
a) Drain Wire 4 x 22 (7/30) AWG TC 
b) Braid TC,70% Coverage, Min. 
4) Jacket 0.050" Wall, Nom.,PVC0.381+/- 0.019
a) Color(s) BLACK
b) Jacket Separator Tissue Tape, 25% Overlap, Min. 
c) Print ALPHA WIRE-* P/N 5660 4C 16 AWG
XTRAGUARD(R) MOTOR SUPPLY CABLE - EXXXXXX
(UL) WTTC 1000V 90C OR (UL) TC-ER 600V 90C DRY
75C WET SUN RES DIR BUR OR MTW 16 AWG ---
LLXXXXXX CSA AWM I/II A/B 90C 600V FT4 CE
ROHS (SEQ FOOTAGE)
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL TC 90°C Dry / 75°C Wet / 600 VRMS
 EXPOSED RUN 
 DIRECT BURIAL 
 SUN RES 
 MTW 90°C Dry / 60°C Wet / 600 VRMS
 WTTC 90°C / 1000 VRMS
2) CSA International AWM I/II A/B 90°C / 600 VRMS
 FT4 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C(static), -5 to 90°C (dynamic)
2) Bend Radius 10X Cable Diameter(static), 15X Cable Diameter(dynamic)
3) Pull Tension 109 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 48 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Ground Capacitance86 pf/ft @1 kHz, Nominal
4) Inductance0.18 µH/ft, Nominal
5) Conductor DCR4.1 Ω/1000ft @20°C, Nominal
6) OA Shield DCR1.8 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Alpha Essentials Tray Cable:

Built to withstand the harshest environments for your communication and control needs, Alpha Essentials tray cables present the perfect solution. We offer both CSA and UL ratings to meet the most stringent industrial applications.  Alpha Wire tray cables come in a variety of configurations which allow for faster installation without the costly need of conduit. 

 

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire