Part # Size (mm2)  # of Elements  Voltage  Jacket Diameter  Shielding  Insulation Material  Jacket Material  Type  Applicable Specifications 
470035CY 0.5  300  7.43  BRAID  PVC  PVC  Multicored  CE, CLASS 5, DIN EN 50290-2-22, DIN EN 6003321-2, EN 60228 CONDUCTORS, IEC 60332-1-2, REACH, ROHS - RoHS Compliance, VDE 0482-3321-2 
(Ctrl+Click if PDF doesn't appear)
  Diameters (mm)
1) Component 1 3 X 1 COND  
a) Conductor 0.50 (20/.177) mm2 Bare Copper 0.91
b) Insulation 0.400 mm Wall, Nom. PVC 1.71+/- 0.08
(1) Print Color
 WHITE
(1) Color(s)

Cond Color Cond Color Cond Color
1 BLACK #1 2 BLACK #2 3 YELLOW/GREEN
c) Cabling 3 COND Cabled  
(1) Twists: 13.6 Twists/meter (min)  
(2) Orientation: Components to be arranged from INSIDE LAYER to OUTSIDE LAYER  
d) Jacket 0.65 mm Wall, Nom.,PVC 5.04+/ 0.20
(1) Color(s) GREY
2) Shield Tinned Copper BRAID Shield,80% Coverage, Min.  
3) Jacket 0.82 mm Wall, Nom.,PVC 7.43 (7.68 Max.)
a) Color(s) Clear, Grey
b) Print ALPHA WIRE-* P/N 470035CY
PRO-MET 300/500V 3G0.5MM2 PVC/PVC/TCB/PVC
MULTI CORE CONTROL CABLE ◁ VDE-REG 8770 ▷
CE ROHS DDDYANN XXXXXXX M
* = Factory Code
1) IEC    
a) Component 1 EN 60228 Conductors, Class 5  
  DIN VDE 0295 Class 5
 
2) Other IEC 60332-1 Flame Behavior  
  DIN EN 50290-2-22 Oil Resistance
 
  UV Resistant  
3) CE: EU Low Voltage Directive 2014/35/EU
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range -40 to 80°C(static), -30 to 70°C (dynamic)
2) Bend Radius 6X Cable Diameter(static), 20X Cable Diameter(dynamic)
3) Sunlight Resistance Yes
Electrical Properties (For Engineering purposes only)
1) Voltage Rating 300/500 VRMS
2) Conductor DCR 39 Ω/Km @20°C, Max.
Packaging Flange x Traverse x Barrel (inches)
a) 300 M 16 x 11 x 8 Continuous length
b) 100 M 12 x 6 x 3.5 Continuous length
c) 50 M 12 x 4.5 x 3.5 Continuous length
  [Spool dimensions may vary slightly]
Pro-Met® industrial cables are designed to perform better, providing consistent and reliable operation. The result is more uptime, fewer errors, and precise operation of equipment. Pro-Met’s round construction makes it easier to install, seal, and route.