Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
58414 Pair  FOIL  300  22  PPVC  PPVC  0.217  CA Prop 65, CSA - C(UL) TYPE CMP, CSA FT6, REACH Regulation (EC 1907/2006), UL CL2P, UL CMP 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 4 X 1 PAIR 
a) Conductor 22 (7/30) AWG BC 0.030
b) Insulation 0.008" Wall, Nom. PVC, Plenum Rated 0.046
(1) Color Code Alpha Wire Color Code A1
Pair Color Pair Color Pair Color
1 BLACK-RED 3 BLACK-GREEN 
2 BLACK-WHITE 4 BLACK-BLUE 
c) Pair 2/Cond Cabled Together 
(1) Twists: 8.0 Twists/foot (min) 
2) Cable Assembly 4 Components Cabled 
a) Twists: 4.8 Twists/foot (min) 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing Out 
b) Drain Wire 24 (7/32) AWG TC 
4) Jacket 0.015" Wall, Nom.,PVC, Plenum Rated0.217 (0.229 Max.)
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N 58414 4PR 22 AWG
SHIELDED 75C CMP(UL) C(UL) OR 75C (UL) CL2P
CE ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL CL2P 75°C
 CMP 75°C
2) CSA International FT6 
 C(UL) TYPE CMP 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-5 to 75°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 48 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Mutual Capacitance38 pf/ft @1 kHz, Nominal
3) Ground Capacitance68 pf/ft @1 kHz, Nominal
4) Characteristic Impedance57 Ω
5) Inductance0.17 µH/ft, Nominal
6) Conductor DCR15.4 Ω/1000ft @20°C, Nominal
7) OA Shield DCR15.9 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 12 x 10 x 5 Continuous length
 [Spool dimensions may vary slightly]

Alpha Essentials Plenum Cable:

We offer a full range of cables for control, computer interconnections, security, alarms, and building energy management systems in a variety of plenum-rated insulation and jacket materials.


Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire