Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Material  Jacket Diameter  Applicable Specifications 
6014C Pair  FOIL  300  22  PVC  0.436  CA Prop 65, CSA CMG, CSA FT4, UL AWM 2493, UL CM, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 9 X 1 PAIR 
a) Conductor 22 (7/30) AWG TC 0.030
b) Insulation 0.010" Wall, Nom. Polypropylene(PP) 0.050
(1) Color Code Alpha Wire Color Code A
Pair Color Pair Color Pair Color
1 BLACK-RED 4 BLACK-BLUE7 BLACK-ORANGE
2 BLACK-WHITE 5 BLACK-BROWN8 RED-GREEN
3 BLACK-GREEN 6 BLACK-YELLOW9 RED-WHITE
c) Pair 2/Cond Cabled Together 
(1) Twists: 8.0 Twists/foot (min) 
Individually Applied:
d) Shield: Foil Free Alum/Mylar Tape, 25% Overlap, Min. 
(1) Foil Direction Foil Facing In 
(2) Drain Wire 22 (7/30) AWG TC 
2) Cable Assembly 9 Components Cabled 
a) Twists: 2.4 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.048" Wall, Nom.,PVC0.436 (0.456 Max.)
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N 6014C 9PR 22 AWG
EXXXXX SHIELDED 75C (UL) C(UL) CMG OR AWM 2493
CE ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL AWM/STYLE 2493 60°C
 CMG 75°C
 VW-1 
2) CSA International C(UL) TYPE CMG 75°C
 FT4 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-20 to 75°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 148 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Characteristic Impedance 60 Ω
3) Inductance 0.18 µH/ft, Nominal
4) Mutual Capacitance 28 pf/ft @1 kHz, Nominal
5) Ground Capacitance 50 pf/ft @1 kHz, Nominal
6) Conductor DCR 16.6 Ω/1000ft @20°C, Nominal
7) Ind. Shield DC Resistance 14.4 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 24 x 14 x 12 Continuous length
b) 500 FT 18 x 12 x 8 Continuous length
c) 100 FT 12 x 10 x 5 Continuous length
 [Spool dimensions may vary slightly]

Communication and Control Cable:

Get Control Of Your Communication and Control Applications

Our line-up of standard communication and control cables gives you maximum choice and fewer tradeoffs. By offering you a comprehensive collection of insulation/jacketing materials, shielding options, and conductor counts, you can easily select the cable that meets your most demanding needs. We have cables that go beyond the ordinary to satisfy rigorous requirements of EMI performance, transmission distances, flexibility, and temperature extremes.

Communication and Control Typical applications:

  • Audio systems: speakers, microphones, intercoms

  • Broadcast and studio

  • Data transmission: RS-232, 422, 485

  • CAD/CAM

  • Computer peripherals

  • Business machines

  • Security systems: alarms, cameras, sensors

  • Control systems

  • Instrumentation systems

  • Point-of-sale systems

  • Banking systems

Low capacitance cables for improved transmission distances and signal integrity.

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire