Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Material  Jacket Diameter  Applicable Specifications 
1827C Composite  UNSHIELDED  300  22+18  PVC  0.247  CA Prop 65, CSA CMG, CSA FT4, UL CM, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 5 X 1 COND 
a) Conductor 22 (7/30) AWG TC 0.030
b) Insulation 0.010" Wall, Nom. PVC 0.050
(1) Color Code Alpha Wire Color Code I
Cond Color Cond Color Cond Color
1 GREEN 3 BROWN5 ORANGE
2 WHITE 4 BLUE 
2) Component 2 2 X 1 COND 
a) Conductor 18 (16/30) AWG TC 0.047
b) Insulation 0.018" Wall, Nom. PVC 0.083
(1) Color Code Alpha Wire Color Code D
Cond Color Cond Color Cond Color
1 BLACK 2 RED 
3) Cable Assembly 7 Components Cabled 
a) Twists: 4.4 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
4) Jacket 0.028" Wall, Nom.,PVC0.247 (0.259 Max.)
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N 1827C 5C 22 AWG 2C 18 AWG
75C (UL) TYPE CM OR C(UL) 60C TYPE CMG FT4
CE ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL CM 75°C
 VW-1 
2) CSA International C(UL) TYPE CMG 60°C
 FT4 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-20 to 75°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 53 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Component 1
a) Capacitance 33 pf/ft @1 kHz, Nominal Conductor to Conductor
b) Inductance0.18 µH/ft, Nominal
c) Conductor DCR16.4 Ω/1000ft @20°C, Nominal
3) Component 2
a) Capacitance 32 pf/ft @1 kHz, Nominal Conductor to Conductor
b) Characteristic Impedance68 Ω
c) Inductance0.18 µH/ft, Nominal
d) Conductor DCR7.2 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 12 x 12 x 3.5 Continuous length
 [Spool dimensions may vary slightly]

Communication and Control Cable:

Get Control Of Your Communication and Control Applications

Our line-up of standard communication and control cables gives you maximum choice and fewer tradeoffs. By offering you a comprehensive collection of insulation/jacketing materials, shielding options, and conductor counts, you can easily select the cable that meets your most demanding needs. We have cables that go beyond the ordinary to satisfy rigorous requirements of EMI performance, transmission distances, flexibility, and temperature extremes.

Communication and Control Typical applications:

  • Audio systems: speakers, microphones, intercoms

  • Broadcast and studio

  • Data transmission: RS-232, 422, 485

  • CAD/CAM

  • Computer peripherals

  • Business machines

  • Security systems: alarms, cameras, sensors

  • Control systems

  • Instrumentation systems

  • Point-of-sale systems

  • Banking systems

Low capacitance cables for improved transmission distances and signal integrity.

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire