Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Material  Jacket Diameter  Applicable Specifications 
1085 Conductor  UNSHIELDED  600  16  25  PVC  0.907  CA Prop 65, UL AWM 2463, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 25 X 1 COND 
a) Conductor 16 (19/.0117) AWG TC 0.059
b) Insulation 0.032" Wall, Nom. PVC 0.123
(1) Color Code Alpha Wire Color Code F
Cond Color Cond Color Cond Color
1 BLACK 10 ORANGE/BLACK19 BLUE/RED
2 WHITE 11 BLUE/BLACK20 RED/GREEN
3 RED 12 BLACK/WHITE21 ORANGE/GREEN
4 GREEN 13 RED/WHITE22 BLACK/WHITE/RED
5 ORANGE 14 GREEN/WHITE23 WHITE/BLACK/RED
6 BLUE 15 BLUE/WHITE24 RED/BLACK/WHITE
7 WHITE/BLACK 16 BLACK/RED25 GREEN/BLACK/WHITE
8 RED/BLACK 17 WHITE/RED 
9 GREEN/BLACK 18 ORANGE/RED 
2) Cable Assembly 25 Components Cabled 
a) Twists: 1.1 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.083" Wall, Nom.,PVC0.907 (0.946 Max.)
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N 1085
RU AWM 2463 VW-1 80C 600V CE ROHS
* = Factory Code
1) UL AWM/STYLE 2463 80°C / 600 VRMS
 VW-1 
2) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-20 to 80°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 511 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 28 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.2 µH/ft, Nominal
4) Conductor DCR4.4 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 48 x 26 x 18 Continuous length
b) 500 FT 30 x 14 x 12 Continuous length
c) 100 FT 24 x 14 x 12 Continuous length
 [Spool dimensions may vary slightly]

Communication and Control Cable:

Get Control Of Your Communication and Control Applications

Our line-up of standard communication and control cables gives you maximum choice and fewer tradeoffs. By offering you a comprehensive collection of insulation/jacketing materials, shielding options, and conductor counts, you can easily select the cable that meets your most demanding needs. We have cables that go beyond the ordinary to satisfy rigorous requirements of EMI performance, transmission distances, flexibility, and temperature extremes.

Communication and Control Typical applications:

  • Audio systems: speakers, microphones, intercoms

  • Broadcast and studio

  • Data transmission: RS-232, 422, 485

  • CAD/CAM

  • Computer peripherals

  • Business machines

  • Security systems: alarms, cameras, sensors

  • Control systems

  • Instrumentation systems

  • Point-of-sale systems

  • Banking systems

Low capacitance cables for improved transmission distances and signal integrity.

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire