部件号 Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
45430/5 Conductor  FOIL  600/1000  18  0.42  CA Prop 65, CE, CSA AWM I/II A/B, CSA FT1, Pennsylvania Bureau of Mine Safety Approved, UL AWM 20238, UL TC, UL WTTC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 5 X 1 COND 
a) Conductor 18 (16/30) AWG Tinned Copper 0.047
b) Insulation 0.032" Wall, Nom. TPE 0.111
(1) Color Code Alpha Wire Color Code E
Cond Color Cond Color Cond Color
1 BLACK 3 RED5 YELLOW
2 BROWN 4 ORANGE 
2) Cable Assembly 5 Components Cabled 
a) Twists: 3.4 Twists/foot (min) 
b) Core Wrap Nonwoven Polyester Tape, 25% Overlap, Min. 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing In 
b) Drain Wire 18 (16/30) AWG Tinned Copper 
4) Jacket 0.055" Wall, Nom.,TPE0.420 (0.441 Max.)
a) Color(s) Slate, Black, Yellow, Orange, Blue, Green, Red, Sand Beige, White
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 45430/5 5C 18 AWG
XTRAGUARD(R) 4 E324185 (UL) TYPE WTTC 90C DRY
1000V OR (UL) TYPE TC 90C DRY 600V OR AWM 20238
125C 600V 18 AWG OR CRU AWM I/II A/B
125C 600V FT1 P-07-KA140023-MSHA CE
(SEQ FOOTAGE)
* = Factory Code
1) UL AWM/STYLE 20238 125°C / 600 VRMS
 TC 90°C / 600 VRMS
 WTTC 90°C / 1000 VRMS
2) CSA International C(RU) AWM I/II A/B FT1 125°C / 600 VRMS
3) Other PENNSYLVANIA BUREAU OF MINE SAFETY APPROVED 
4) CE:EU Low Voltage Directive 2006/95/EC
1) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range-50 to 125°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 75 Lbs, Maximum
4) Sunlight Resistance Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600/1000 VRMS
2) Capacitance 17.6 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Ground Capacitance32 pf/ft @1 kHz, Nominal
4) Inductance0.22 µH/ft, Nominal
5) Conductor DCR7.2 Ω/1000ft @20°C, Nominal
6) OA Shield DCR5.7 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Xtra-Guard ® 4 – 抵抗极端温度适用于高温、低温和泄漏环境 High TemperatureLow TemperatureUltraviolet LightEMI Noise

  • 温度耐受性极高,适用于 -50°C 到 +125°C 的工作环境
  • 高性能热塑性橡胶绝缘和护套,低温柔韧性是普通聚氯乙烯的三倍
  • 具有中等的耐油、耐溶剂、耐腐蚀和耐燃料性能
  • 所有护套颜色都具有出色的紫外线照射稳定性
  • UL TC 600 V 和 PLTC 300 V,适合电缆槽应用(24 AWG 除外)
  • 经宾夕法尼亚州深井采矿安全局的认证,适用于整个矿区的监控系统(14 AWG 除外)
  • 与 Alpha 高性能屏蔽系统 Supra-Shield® 结合使用时,具有优异的抗电磁干扰/射频干扰性
样品申请 下载产品手册 咨询线缆专家

¿需要更多的自定义设计吗?请查看我们的

获取报价 资源中心
AlphaWire