# de pieza Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
35010/15 Conductor  UNSHIELDED  300  22  15  0.297  CA Prop 65 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 15 X 1 COND 
a) Conductor 22 (7/30) AWG TC 0.030
b) Insulation 0.010" Wall, Nom. PVC, Semi Rigid 0.050
(1) Color Code Alpha Wire Color Code E
Cond Color Cond Color Cond Color
1 BLACK 6 GREEN11 WHITE/BLACK
2 BROWN 7 BLUE12 WHITE/BROWN
3 RED 8 VIOLET13 WHITE/RED
4 ORANGE 9 SLATE14 WHITE/ORANGE
5 YELLOW 10 WHITE15 WHITE/YELLOW
2) Cable Assembly 15 Components Cabled 
a) Twists: 3.7 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.032" Wall, Nom.,Polyethylene (PE)0.297 (0.313 Max.)
a) Color(s) Slate, Black, Yellow, Orange, Blue, Green, Red, Sand Beige, White
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 35010/15 15C 22 AWG
XTRAGUARD(R) 3 80C 300 VOLTS CE ROHS
(SEQ FOOTAGE)
* = Factory Code
1) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range-30 to 80°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 82 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Capacitance 23.5 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.18 µH/ft, Nominal
4) Conductor DCR16.4 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Xtra-Guard® 3 - Tendido subterráneo directo-no requiere conducto Ultraviolet LightOil, Chemicals, Solvents, FuelsDirect BurialEMI Noise

    • El cable de exteriores preferido para el tendido subterráneo directo 
    • Seis veces la resistencia hídrica del PVC 
    • Presenta una cubierta exterior de polietileno especialmente formulada de excelente vida útil y estabilidad a la luz ultravioleta en todos los colores de cubierta exterior 
    • Resistente a los efectos de la intemperie, la humedad y el envejecimiento por rayos UV sin el uso costoso de tuberías 
    • Supra-Shield® brinda excepcional protección contra el ruido conductivo o eléctrico en ambientes de alta y baja frecuencia donde la interferencia electromagnética es penetrante

Solicite una muestra Descargar el catálogo Consultar a un experto

¿Necesita un diseño más personalizado?

Solicite un presupuesto personalizado Recursos
AlphaWire