# de pieza Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
V16016 Conductor  FOIL/BRAID  600  16  0.545  CA Prop 65, CE, CSA AWM I/II A/B, CSA FT4, UL DIRECT BURIAL, UL EXPOSED RUN, UL RHW-2Wet/Dry, UL SUN RES, UL TC, UL XHHW-2Wet/Dry 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 4 X 1 COND 
a) Conductor 16 (26/30) AWG Tinned Copper 0.059
b) Insulation 0.046" Wall, Nom. XLPE 0.155
(1) Separator Paper Tape, 10% Overlap, Min. 
(2) Color(s)  
Cond Color Cond Color Cond Color
1 BLACK#1 3 BLACK#3 
2 BLACK#2 4 GREEN OR GREEN/YELLOW 
2) Cable Assembly 4 Components Cabled 
a) Twists: 2.2 Twists/foot (min) 
3) Shield: A/P/A Tape, 25% Overlap, Min. 
a) Drain Wire 16 (26/30) AWG Tinned Copper 
b) Braid Tinned Copper,85% Coverage, Min. 
4) Jacket 0.065" Wall, Nom.,PVC0.545+/- 0.016
a) Color(s) BLACK
b) Jacket Separator Tissue Tape, 25% Overlap, Min. 
c) Print ALPHA WIRE-* P/N V16016
4C16 SHIELDED (UL) 1000V FLEXIBLE MOTOR
SUPPLY CABLE OR WTTC 90C WET/DRY OR 600V TC-ER
XHHW-2 CDRS XLPE/PVC 90C WET/DRY
OR 4C16 C(UL) 600V CIC TC 90C WET/DRY FT4 (-25C)
--- P-07-KA080006-MSHA --- LLXXXXXX CSA AWM I/II
A/B 1000V 90C FT4 CE ROHS (SEQ FOOTAGE)
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL   
a) Component 1 RHW-2Wet/Dry 90°C Dry / 90°C Wet / 600 VRMS
 XHHW-2Wet/Dry 90°C Dry / 90°C Wet / 600 VRMS
b) Overall TC 90°C Dry / 90°C Wet / 600 VRMS
 EXPOSED RUN 
 DIRECT BURIAL 
 SUN RES 
 1000V Flexible Motor Supply Cable 
 WTTC 90°C / 1000 VRMS
2) CSA International AWM I/II A/B 90°C / 1000 VRMS
 FT4 
 C(UL) TC 90°C Dry / 90°C Wet / 600 VRMS
 C(UL) CIC CONTROL 90°C Dry / 90°C Wet / 600 VRMS
 C(UL) -25C 
3) Other PMSHA Specification 
4) CE:EU Low Voltage Directive 2006/95/EC
1) EU Directive 2002/95/EC(RoHS):
 All materials used in the manufacture of this part are in compliance with EU Directive 2002/95/EU regarding the restriction of use of certain hazardous substances in electrical and electronic equipment. Consult Alpha Wire's web site for compliance Date of Manufacture.
2) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range -40 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 116 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
6) Copper Weight 71 Lbs/1000Ft
7) Cable Weight 200 Lbs/1000Ft
Electrical Properties (For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Characteristic Impedance 90 Ω
3) Inductance 0.229 µH/ft, Nominal
4) Mutual Capacitance 21 pf/ft @1 kHz, Nominal
5) Ground Capacitance 38 pf/ft @1 kHz, Nominal
6) Conductor DCR 4.4 Ω/1000ft @20°C, Nominal
7) OA Shield DCR 1.4 Ω/1000ft @20°C, Nominal
8) Current 14.4 amps per conductor @30°C, Maximum
9) Insulation Resistance 300 MΩ/MFt (Est.)
1) Packaging
a) Bulk(Made-to-order)  

Optimizado para unidades de transmisión de frecuencia variable, los cables de VFD de la serie V de Alpha Wire ofrecen un desempeño mecánico y eléctrico líder en la industria.

Características clave de la Serie V: 
    • Disponibilidad en 4 conductores (con y sin par de frenos) y 3 conductores (NUEVO) 
    • 16 a 4/0 AWG 
    • Par de frenos de 14 AWG 
    • Aislamiento de polietileno reticulado 
    • Cubierta exterior de PVC 
    • Diámetro pequeño 
    • Capacitancia baja para brindar mejor transmisión de señales 
    • UL tipo TC-ER (600 voltios) 
    • CSA I/II A/B 1000 voltios FT4 
    • Tendido subterráneo directo 
    • Resistente a la luz solar

Solicite una muestra Descargar el catálogo Consultar a un experto

¿Necesita un diseño más personalizado?

Solicite un presupuesto personalizado Recursos
AlphaWire