Part # Voltage  AWG  Stranding  Insulation Thickness  Nominal Diameter  Insulation Material  Applicable Specifications 
PV1230 2000  12  65/30  0.063  0.286  XLPE  CSA RW 90, REACH Regulation (EC 1907/2006), ROHS - RoHS Compliance, UL PV WIRE, UL SUN RES, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 1 X 1 HOOKUP 
a) Conductor 12 (65/30) AWG TC 0.093
b) Insulation 0.063" Wall, Nom. XLPE 0.222+/- 0.006
(1) Separator Polyester Tape, 10% Overlap, Min. 
(2) Color(s) BLACK
2) Jacket 0.032" Wall, Nom.,PVC0.286 (0.299 Max.)
a) Color(s) BLACK
b) Print ALPHA WIRE-* P/N PV1230
12 AWG (UL) PV WIRE 90C WET/DRY 2000V SUN RES
-40C VW-1 CSA LL7874 12 AWG RW90 1000V
ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL VW-1 
 SUN RES 
 -40C 
 PV WIRE 90°C Dry / 90°C Wet / 2000 VRMS
2) CSA International RW90 90°C Dry / 90°C Wet / 1000 VRMS
1) EU Directive 2011/65/EU(RoHS2):
 All materials used in the manufacture of this part are in compliance with European Directive 2011/65/EU regarding the restriction of use of certain hazardous substances in electrical and electronic equipment. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
Physical & Mechanical Properties
1) Temperature Range-40 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 51 Lbs, Maximum
4) Sunlight Resistance Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 2000 VRMS
2) Inductance 0.06 µH/ft, Nominal
3) Conductor DCR 1.75 Ω/1000ft @20°C, Nominal
4) Current 40 amps per conductor @30°C, Maximum
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 16 x 11 x 8 Continuous length
b) 100 FT 12 x 4.5 x 3.5 Continuous length
 [Spool dimensions may vary slightly]

Our photovoltaic wire gives you reliable wire to meet UL 4703.

Features:

  • Sunlight, ozone, and UV resistant
  • Moisture resistant
  • RoHS compliant
  • REACH compliant
  • -40°C to +90°C temperature range