Construction
| Diameters (In) |
1) Component 1 | 1 X 1 PAIR | |
a) Conductor | 18 (16/30) AWG Tinned Copper | 0.047 |
b) Insulation | 0.016" Wall, Nom. TPE | 0.079 |
(1) Color Code | Alpha Wire Color Code B |
Pair | Color | Pair | Color | Pair | Color | 1 | WHITE-BLACK | | | | |
|
c) Cabling | 2 COND Cabled | |
(1) Twists: | 5.3 Twists/foot (min) | |
(2) Orientation: | Components to be arranged from INSIDE LAYER to OUTSIDE LAYER | |
2) Core Wrap | Nonwoven Polyester Tape, 25% Overlap, Min. | |
3) Jacket | 0.045" Wall, Nom.,TPE | 0.252 (0.263 Max.) |
a) Color(s) | Slate, Black, Yellow, Orange, Blue, Green, Red, Sand Beige, White |
b) Ripcord | 1 End 810 Denier Nylon | |
c) Print | ALPHA WIRE-* P/N 45031 1PR 18 AWG XTRAGUARD(R) 4 (UL) TYPE PLTC 105C SUN RES OR AWM 21916 125C 300 V OR CRU AWM I/II A/B 125C 300V FT1 P-07-KA140023-MSHA CE ROHS (SEQ FOOTAGE) * = Factory Code
|
Applicable Specifications
1) UL | AWM/STYLE 21916 | 125°C / 300 VRMS |
| PLTC | 105°C |
| SUN RES | |
2) CSA International | C(RU) AWM I/II A/B FT1 | 125°C / 300 VRMS |
| SUN RES (Black only) | |
3) Other | PENNSYLVANIA BUREAU OF MINE SAFETY APPROVED | |
4) CE: | EU Low Voltage Directive 2014/35/EC |
Environmental
1) CE: EU Directive 2011/65/EU(RoHS2): |
| This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C. |
2) REACH Regulation (EC 1907/2006): |
| This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration. |
3) California Proposition 65: | Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information. |
Properties
Physical & Mechanical Properties |
---|
1) Temperature Range | -50 to 125°C |
2) Bend Radius | 10X Cable Diameter |
3) Pull Tension | 25 Lbs, Maximum |
4) Sunlight Resistance | Yes |
Electrical Properties | (For Engineering purposes only) |
---|
1) Voltage Rating | 300 VRMS |
2) Mutual Capacitance | 17 pF/ft @1 kHz, Nominal
|
3) Characteristic Impedance | 91 Ω
|
4) Inductance | 0.18 µH/ft, Nominal
|
5) Conductor DCR | 7 Ω/1000ft @20°C, Nominal
|
Other
Packaging | Flange x Traverse x Barrel (inches) |
a) 1000 FT | 12 x 12 x 3.5 Continuous length |
b) 500 FT | 12 x 6 x 3.5 Continuous length |
c) Bulk(Made-to-order) | |
| [Spool dimensions may vary slightly] |
Notes: |
a) Print legend will contain CSA SUN RES on black cables only. |
Xtra-Guard® 4 - Handles extreme hot and cold temperatures 




- Extended-temperature cable with a temperature range from -50°C to +125°C
- Features a high-performance TPE insulation and jacket offering three times the low-temperature flexibility of ordinary PVC
- Outstanding ultraviolet light stability in all jacket colors
- UL Rated TC 600 V and PLTC 300 V for cable tray applications (except 24 AWG)
- Pennsylvania Bureau Deep Mining Safety approved for mine-wide monitoring systems
- Provides exceptional protection against EMI interference when Supra-Shield is specified