Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
35450/9 Conductor  FOIL  600  14  0.635  CA Prop 65, CSA TEW 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 9 X 1 COND 
a) Conductor 14 (41/30) AWG Tinned Copper 0.070
b) Insulation 0.032" Wall, Nom. PVC 0.134
(1) Color Code Alpha Wire Color Code E
Cond Color Cond Color Cond Color
1 BLACK 4 ORANGE7 BLUE
2 BROWN 5 YELLOW8 VIOLET
3 RED 6 GREEN9 SLATE
2) Cable Assembly 9 Components Cabled 
a) Twists: 1.7 Twists/foot (min) 
b) Orientation: Components to be arranged from INSIDE LAYER to OUTSIDE LAYER 
c) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing In 
b) Drain Wire 14 (41/30) AWG Tinned Copper 
4) Jacket 0.063" Wall, Nom.,Polyethylene (PE)0.621 (0.648 Max.)
a) Color(s) Slate, Black, Yellow, Orange, Blue, Green, Red, Sand Beige, White
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 35450/9 9C 14 AWG
XTRAGUARD(R) 3 80C 600 VOLTS CE ROHS
(SEQ FOOTAGE)
* = Factory Code
1) UL   
a) Component 1 AWM/STYLE 1015 105°C / 600 VRMS
2) CE:EU Low Voltage Directive 2014/35/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-30 to 80°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 322 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 40 pF/ft @1 kHz, Nominal Conductor to Conductor
3) Ground Capacitance72 pF/ft @1 kHz, Nominal
4) Inductance0.19 µH/ft, Nominal
5) Conductor DCR2.8 Ω/1000ft @20°C, Nominal
6) OA Shield DCR2.4 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Xtra-Guard® 3 - Direct burial—no conduit needed Ultraviolet LightOil, Chemicals, Solvents, FuelsDirect BurialEMI Noise

  • The preferred outdoor cable for direct burial
  • 6 times the water resistance of PVC
  • Features a specially formulated polyethylene jacket for outstanding service life and ultraviolet light stability in all jacket colors
  • Resistant to the effects of weathering, moisture, and UV aging without the costly use of conduit
  • Supra-Shield® provides exceptional protection against conducted or electrical noise in high- and low- frequency environments where EMI interference is pervasive

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire