Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
M10107KW Conductor  UNSHIELDED  600  10  0.652  CA Prop 65, CE, CSA AWM I/II A/B, CSA FT4, UL DIRECT BURIAL, UL EXPOSED RUN, UL MTW, UL OIL RES I, UL SUN RES, UL TC, UL WTTC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 7 X 1 COND 
a) Conductor 10 (105/30) AWG BC 0.118
b) Insulation 0.022" Wall, Nom. PVC/ 0.005" Wall NYLON 0.172
(1) Print ALPHANUMERIC NUMBERS - 1-ONE ALTERNATING AND
INVERTED
(2) Color Code Alpha Wire Color Code KX
Cond Color Cond Color Cond Color
1 GREEN/YELLOW 4 BLACK#37 BLACK#6
2 BLACK#1 5 BLACK#4 
3 BLACK#2 6 BLACK#5 
2) Cable Assembly 7 Components Cabled 
a) Twists: 1.7 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.065" Wall, Nom.,PVC0.652+/- 0.031
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N M10107KW 7C 10 AWG (5.32mm2)
SERIES M (UL) WTTC 90C DRY 75C WET 1000V OR
(UL) TC-ER 90C DRY 75C WET 600V
SUN RES DIR BUR OIL RES I OR MTW 10 AWG
--- LLXXXXXX CSA AWM I/II A/B 90C 600V FT4
CE ROHS (DATE CODE) (SEQ FOOTAGE)
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL TC 90°C Dry / 75°C Wet / 600 VRMS
 EXPOSED RUN 
 SUN RES 
 DIRECT BURIAL 
 OIL RES I 
 MTW 90°C Dry / 60°C Wet / 600 VRMS
 WTTC 90°C / 1000 VRMS
2) CSA International FT4 
 AWM I/II A/B 90°C / 600 VRMS
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 577 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 36 pf/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.16 µH/ft, Nominal
4) Conductor DCR1.02 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Alpha Wire's Series M control cable offers industry-leading mechanical and electrical performance for stationary cable trays.

Series M Key features:

  • 18 – 8 AWG
  • 3 – 65 conductors
  • PVC/nylon insulation
  • Oil-resistant PVC jacket
  • UL Type TC-ER (600 V)
  • UL Type MTW (600V)
  • UL Type WTTC (600V)
  • UL Type PLTC (300 V) (18-12AWG only)
  • Direct burial
  • Sunlight resistant
  • UL Oil Res. I

Request a Sample Download Brochure Consult a Cable Expert