Part # Type  AWG  Voltage  Shielding  # of Elements  Jacket Material  Insulation Material  Jacket Diameter  Applicable Specifications 
M8846020 Triad  16  600  Ind/Overall Foil  PVC  PVC/NYLON  0.578  CA Prop 65, UL DIRECT BURIAL, UL EXPOSED RUN, UL SUN RES, UL TC 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 2 X 1 TRIAD 
a) Conductor 16 (7/.0192) AWG BC 0.058
b) Insulation 0.016" Wall, Nom. PVC/ 0.005" Wall NYLON 0.100
(1) Print ALPHA NUMERIC NUMBERS - WHITE CONDUCTOR ONLY
(ONE-1) ALTERNATE INVERTED 2"SPACING(CTR. TO CTR.)
(2) Color(s)  
Triad Color Triad Color Triad Color
1 BLACK-WHITE#1-RED 2 BLACK-WHITE#2-RED 
c) Pair 3/Cond Cabled Together 
(1) Twists: 4.0 Twists/foot (min) 
Individually Applied:
d) Shield: Foil Free Alum/Mylar Tape, 25% Overlap, Min. 
(1) Foil Direction Foil Facing In 
(2) Drain Wire 18 (7/.0152) AWG TC 
2) Cable Assembly 2 Components Cabled 
a) Twists: 1.8 Twists/foot (min) 
b) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing In 
b) Drain Wire 18 (7/.0152) AWG TC 
4) Jacket 0.065" Wall, Nom.,PVC0.578 (0.605 Max.)
a) Color(s) BLACK
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N M8846020 2TRIAD 16 AWG
EXXXXXX (UL) TYPE TC-ER 600V 90C DRY 75C WET
SUN. RES. DIR. BUR. CE ROHS
* = Factory Code
1) UL TC 90°C / 600 VRMS
 SUN RES 
 DIRECT BURIAL 
 EXPOSED RUN 
2) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-25 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 160 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Mutual Capacitance45 pf/ft @1 kHz, Nominal
3) Ground Capacitance81 pf/ft @1 kHz, Nominal
4) Characteristic Impedance48 Ω
5) Inductance0.18 µH/ft, Nominal
6) Conductor DCR4.2 Ω/1000ft @20°C, Nominal
7) Component Shield DCR6.1 Ω/1000ft @20°C, Nominal
8) OA Shield DCR5.2 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 30 x 14 x 12 Continuous length
b) 500 FT 24 x 14 x 12 Continuous length
c) 100 FT 16 x 11 x 8 Continuous length
d) Bulk(Made-to-order) 
 [Spool dimensions may vary slightly]

Alpha Essentials Tray Cable:

Built to withstand the harshest environments for your communication and control needs, Alpha Essentials tray cables present the perfect solution. We offer both CSA and UL ratings to meet the most stringent industrial applications.  Alpha Wire tray cables come in a variety of configurations which allow for faster installation without the costly need of conduit. 

 

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire