Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Material  Jacket Diameter  Applicable Specifications 
6203C Pair  FOIL  300  24  PVC  0.272  CA Prop 65, CSA CMG, CSA FT4, UL AWM 2919, UL CM, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 3 X 1 PAIR 
a) Conductor 24 (7/32) AWG TC 0.024
b) Insulation 0.016" Wall, Nom. Polyethylene, Foam 0.056
(1) Color Code Alpha Wire Color Code A
Pair Color Pair Color Pair Color
1 BLACK-RED 2 BLACK-WHITE3 BLACK-GREEN
c) Pair 2/Cond Cabled Together 
(1) Twists: 8.0 Twists/foot (min) 
2) Cable Assembly 3 Components Cabled 
a) Twists: 4.0 Twists/foot (min) 
3) Shield: Alum/Mylar Tape, 25% Overlap, Min. 
a) Foil Direction Foil Facing Out 
b) Drain Wire 24 (7/32) AWG TC 
4) Jacket 0.035" Wall, Nom.,PVC0.272 (0.286 Max.)
a) Color(s) SLATE
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 6203C 3PR 24 AWG
SHIELDED 75C (UL) TYPE CM OR AWM 2919 LOW VOLTAGE
COMPUTER CABLE --- LLXXXXXX CSA TYPE CMG 60C FT4
CE ROHS
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL AWM/STYLE 2919 80°C / 30 VRMS
 CM 75°C
 VW-1 
2) CSA International CMG 60°C
 FT4 
3) CE:EU Low Voltage Directive 2006/95/EC
1) CE: EU Directive 2011/65/EU(RoHS2), EU Directive 2015/863/EU (RoHS3):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011 and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-20 to 80°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 24.6 Lbs, Maximum
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Characteristic Impedance 105 Ω +/- 10
3) Mutual Capacitance 12.5 pf/ft @1 kHz, Nominal
4) Ground Capacitance 22 pf/ft @1 kHz, Nominal
5) Velocity of Propagation 78 %
6) Attenuation, Max dB/100ft 0.25 @ 100 kHz
  0.8 @ 1 MHz
  5.8 @ 50 MHz
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 12 x 12 x 3.5 Continuous length
b) 500 FT 12 x 10 x 5 Continuous length
 [Spool dimensions may vary slightly]

Communication and Control Cable:

Get Control Of Your Communication and Control Applications

Our line-up of standard communication and control cables gives you maximum choice and fewer tradeoffs. By offering you a comprehensive collection of insulation/jacketing materials, shielding options, and conductor counts, you can easily select the cable that meets your most demanding needs. We have cables that go beyond the ordinary to satisfy rigorous requirements of EMI performance, transmission distances, flexibility, and temperature extremes.

Communication and Control Typical applications:

  • Audio systems: speakers, microphones, intercoms

  • Broadcast and studio

  • Data transmission: RS-232, 422, 485

  • CAD/CAM

  • Computer peripherals

  • Business machines

  • Security systems: alarms, cameras, sensors

  • Control systems

  • Instrumentation systems

  • Point-of-sale systems

  • Banking systems

Low capacitance cables for improved transmission distances and signal integrity.

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire