Teil Nr. Voltage  AWG  Stranding  Insulation Thickness  Insulation Diameter  Insulation Material  Applicable Specifications 
PV1430 2000  14  41/30  0.063  0.267  XLPE  CSA RW 90, REACH Regulation (EC 1907/2006), ROHS - RoHS Compliance, UL PV WIRE, UL SUN RES, UL VW-1 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 1 X 1 HOOKUP 
a) Conductor 14 (41/30) AWG TC 0.074
b) Insulation 0.063" Wall, Nom. XLPE 0.203+/- 0.006
(1) Separator Polyester Tape, 10% Overlap, Min. 
(2) Color(s) BLACK
2) Jacket 0.032" Wall, Nom.,PVC0.267 (0.280 Max.)
a) Color(s) Black, Red
b) Print ALPHA WIRE-* P/N PV1430
-40C VW-1 CSA LL7874 14 AWG RW90 1000V
* = Factory Code
[Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
1) UL VW-1 
 PV WIRE 90°C Dry / 90°C Wet / 2000 VRMS
2) CSA International RW90 90°C Dry / 90°C Wet / 1000 VRMS
1) EU Directive 2011/65/EU(RoHS2):
 All materials used in the manufacture of this part are in compliance with European Directive 2011/65/EU regarding the restriction of use of certain hazardous substances in electrical and electronic equipment. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
Physical & Mechanical Properties
1) Temperature Range-40 to 90°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 32 Lbs, Maximum
4) Sunlight Resistance Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 2000 VRMS
2) Inductance 0.07 µH/ft, Nominal
3) Conductor DCR 2.8 Ω/1000ft @20°C, Nominal
4) Current 35 amps per conductor @30°C, Maximum
PackagingFlange x Traverse x Barrel (inches)
a) 1000 FT 12 x 12 x 3.5 Continuous length
b) 100 FT 12 x 4.5 x 3.5 Continuous length
 [Spool dimensions may vary slightly]
a) Red jacket available by special order only, Minimums may apply.

Unsere Photovoltaikleitungen geben Ihnen Flexibilität bei der Auswahl entsprechend den Anforderungen an UL 4703 und UL 4703 PV/TÜV 2 PFG 1169 Leitungen.


  • Sonnenlicht-, Ozon- und UV-beständig
  • Feuchtigkeitsbeständig
  • RoHS konform
  • REACH konform
  • Temperaturbereich -40°C bis +90°C

Formular zur Musterbestellung Broschüre herunterladen Konsultieren Sie einen Kabel-Experte

brauchen eine einzigartige Konstruktion?

Fordern Sie ein kundenspezifisches Angebot Ressourcen